{"title":"冷却系统效率分析","authors":"Yu. K. Dmitriev","doi":"10.23968/2500-0055-2022-7-4-49-59","DOIUrl":null,"url":null,"abstract":"Introduction: The main task of cooling systems in the machine room of a data center is to maintain optimal air parameters at the inlet to IT equipment in accordance with the applicable regulatory documents. If the value of air temperature at the inlet to IT equipment exceeds the optimal value, then so-called hot spots occur — the operation of IT equipment in such places can lead to its overheating and failure. The main reason for the occurrence of hot spots is the violation of air circulation between the hot and cold aisles. Purpose of the study: We aimed to analyze the influence of different methods of hot aisle isolation on the efficiency of IT equipment cooling. Methods: We performed modeling of different methods of hot aisle isolation at different capacity values of IT equipment in the STAR-CCM+ program. Result: As a result of studying temperature and air conditions in a data center, we found the most rational way of isolating the hot aisle — top horizontal containments with vertical blind panels in the free rack space.","PeriodicalId":52295,"journal":{"name":"Architecture and Engineering","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2022-12-29","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"ANALYSIS OF COOLING SYSTEM EFFICIENCY\",\"authors\":\"Yu. K. Dmitriev\",\"doi\":\"10.23968/2500-0055-2022-7-4-49-59\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Introduction: The main task of cooling systems in the machine room of a data center is to maintain optimal air parameters at the inlet to IT equipment in accordance with the applicable regulatory documents. If the value of air temperature at the inlet to IT equipment exceeds the optimal value, then so-called hot spots occur — the operation of IT equipment in such places can lead to its overheating and failure. The main reason for the occurrence of hot spots is the violation of air circulation between the hot and cold aisles. Purpose of the study: We aimed to analyze the influence of different methods of hot aisle isolation on the efficiency of IT equipment cooling. Methods: We performed modeling of different methods of hot aisle isolation at different capacity values of IT equipment in the STAR-CCM+ program. Result: As a result of studying temperature and air conditions in a data center, we found the most rational way of isolating the hot aisle — top horizontal containments with vertical blind panels in the free rack space.\",\"PeriodicalId\":52295,\"journal\":{\"name\":\"Architecture and Engineering\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-12-29\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Architecture and Engineering\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.23968/2500-0055-2022-7-4-49-59\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q1\",\"JCRName\":\"Engineering\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Architecture and Engineering","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.23968/2500-0055-2022-7-4-49-59","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"Engineering","Score":null,"Total":0}
引用次数: 0

摘要

简介:数据中心机房冷却系统的主要任务是根据适用的法规文件,保持IT设备入口处的最佳空气参数。如果IT设备入口处的空气温度值超过了最佳值,那么就会出现所谓的热点——IT设备在这些地方的运行可能会导致其过热和故障。出现热点的主要原因是冷热通道之间的空气循环受到破坏。研究目的:我们旨在分析不同的热通道隔离方法对IT设备冷却效率的影响。方法:我们在STAR-CCM+程序中,对不同IT设备容量值下的不同热通道隔离方法进行了建模。结果:通过研究数据中心的温度和空气条件,我们找到了隔离热通道的最合理方法——在空闲机架空间中使用带有垂直盲板的顶部水平容器。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
ANALYSIS OF COOLING SYSTEM EFFICIENCY
Introduction: The main task of cooling systems in the machine room of a data center is to maintain optimal air parameters at the inlet to IT equipment in accordance with the applicable regulatory documents. If the value of air temperature at the inlet to IT equipment exceeds the optimal value, then so-called hot spots occur — the operation of IT equipment in such places can lead to its overheating and failure. The main reason for the occurrence of hot spots is the violation of air circulation between the hot and cold aisles. Purpose of the study: We aimed to analyze the influence of different methods of hot aisle isolation on the efficiency of IT equipment cooling. Methods: We performed modeling of different methods of hot aisle isolation at different capacity values of IT equipment in the STAR-CCM+ program. Result: As a result of studying temperature and air conditions in a data center, we found the most rational way of isolating the hot aisle — top horizontal containments with vertical blind panels in the free rack space.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
Architecture and Engineering
Architecture and Engineering Engineering-Architecture
CiteScore
1.80
自引率
0.00%
发文量
26
审稿时长
7 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信