超高压750kV避雷器单段早期阻尼缺陷综合诊断与分析

Yunxiao Bai, Libing Zhou, Huiting Yang, Wenhua Luo, Wentao Chen, Longxiang Yuan
{"title":"超高压750kV避雷器单段早期阻尼缺陷综合诊断与分析","authors":"Yunxiao Bai, Libing Zhou, Huiting Yang, Wenhua Luo, Wentao Chen, Longxiang Yuan","doi":"10.1109/IAEAC47372.2019.8997821","DOIUrl":null,"url":null,"abstract":"With the extention of the arrester’s running time, there appears the situation that a single section of extrahigh voltage 750kV four series surge arrester may get damp and deteriorated.Once subjected to over-voltage intrusion, a serious situation may even lead to a single section of arrester’s explosion, which will bring a very negative impact to the system over-voltage protection.Through the on-line monitoring of the arrester, it is found that the leakage current of an ultrahigh voltage 750kV arrester became over-limited, we carried out full current and resistive current live detection for the whole arrester and blackout test for single section.We analyzed the data and disintegrated the single section. It is concluded that, for the extrahigh voltage 750kV four series surge arrester, especially for early hidden defects, in terms of live detection, it should be effective to combine the on-line monitoring of arrester, live detection, we should pay attention to data accumulation and development trend.In terms of blackout test, DC leakage test is still the most reliable way to diagnose the arrester defect. Therefore, we should strengthen the on-line monitoring and charge detection data accumulation,and also focus on the development trend and combine with the blackout plan to carry out the DC leakage test actively. In this way we can detect early latent fault of single-stage arrester in time, and provide over-voltage protection correctly.","PeriodicalId":164163,"journal":{"name":"2019 IEEE 4th Advanced Information Technology, Electronic and Automation Control Conference (IAEAC)","volume":"42 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2019-12-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Comprehensive Diagnosis and Analysis of Early Damp Defects On a Single Section of EHV 750kV Arrester\",\"authors\":\"Yunxiao Bai, Libing Zhou, Huiting Yang, Wenhua Luo, Wentao Chen, Longxiang Yuan\",\"doi\":\"10.1109/IAEAC47372.2019.8997821\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"With the extention of the arrester’s running time, there appears the situation that a single section of extrahigh voltage 750kV four series surge arrester may get damp and deteriorated.Once subjected to over-voltage intrusion, a serious situation may even lead to a single section of arrester’s explosion, which will bring a very negative impact to the system over-voltage protection.Through the on-line monitoring of the arrester, it is found that the leakage current of an ultrahigh voltage 750kV arrester became over-limited, we carried out full current and resistive current live detection for the whole arrester and blackout test for single section.We analyzed the data and disintegrated the single section. It is concluded that, for the extrahigh voltage 750kV four series surge arrester, especially for early hidden defects, in terms of live detection, it should be effective to combine the on-line monitoring of arrester, live detection, we should pay attention to data accumulation and development trend.In terms of blackout test, DC leakage test is still the most reliable way to diagnose the arrester defect. Therefore, we should strengthen the on-line monitoring and charge detection data accumulation,and also focus on the development trend and combine with the blackout plan to carry out the DC leakage test actively. In this way we can detect early latent fault of single-stage arrester in time, and provide over-voltage protection correctly.\",\"PeriodicalId\":164163,\"journal\":{\"name\":\"2019 IEEE 4th Advanced Information Technology, Electronic and Automation Control Conference (IAEAC)\",\"volume\":\"42 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2019-12-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2019 IEEE 4th Advanced Information Technology, Electronic and Automation Control Conference (IAEAC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/IAEAC47372.2019.8997821\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2019 IEEE 4th Advanced Information Technology, Electronic and Automation Control Conference (IAEAC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/IAEAC47372.2019.8997821","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

随着避雷器使用时间的延长,出现了特高压750kV四串联避雷器单段受潮变质的情况。一旦受到过电压侵入,严重的情况下甚至可能导致避雷器单段发生爆炸,对系统过电压保护带来非常不利的影响。通过对某超高压750kV避雷器的在线监测,发现避雷器的漏电流出现过限现象,对整个避雷器进行了全电流和阻性电流的活检,对单段避雷器进行了断电试验。我们分析了数据并分解了单个部分。得出结论,对于特高压750kV四串联避雷器,特别是对于早期隐藏缺陷,在带电检测方面,应将避雷器的在线监测、带电检测相结合,应注意数据的积累和发展趋势。在停电试验方面,直流漏电试验仍然是诊断避雷器缺陷最可靠的方法。因此,既要加强在线监测和充电检测数据积累,又要关注发展趋势,结合停电预案积极开展直流漏电试验。这样可以及时发现单级避雷器的早期潜在故障,正确提供过电压保护。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Comprehensive Diagnosis and Analysis of Early Damp Defects On a Single Section of EHV 750kV Arrester
With the extention of the arrester’s running time, there appears the situation that a single section of extrahigh voltage 750kV four series surge arrester may get damp and deteriorated.Once subjected to over-voltage intrusion, a serious situation may even lead to a single section of arrester’s explosion, which will bring a very negative impact to the system over-voltage protection.Through the on-line monitoring of the arrester, it is found that the leakage current of an ultrahigh voltage 750kV arrester became over-limited, we carried out full current and resistive current live detection for the whole arrester and blackout test for single section.We analyzed the data and disintegrated the single section. It is concluded that, for the extrahigh voltage 750kV four series surge arrester, especially for early hidden defects, in terms of live detection, it should be effective to combine the on-line monitoring of arrester, live detection, we should pay attention to data accumulation and development trend.In terms of blackout test, DC leakage test is still the most reliable way to diagnose the arrester defect. Therefore, we should strengthen the on-line monitoring and charge detection data accumulation,and also focus on the development trend and combine with the blackout plan to carry out the DC leakage test actively. In this way we can detect early latent fault of single-stage arrester in time, and provide over-voltage protection correctly.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信