Bagus Ferdiansah, Agus Margiantono, Fahrudin Ahmad
{"title":"分析银行电容对电动势值和伏电压值的影响","authors":"Bagus Ferdiansah, Agus Margiantono, Fahrudin Ahmad","doi":"10.37905/jjeee.v5i2.20893","DOIUrl":null,"url":null,"abstract":"Listrik merupakan salah satu kebutuhan pokok masyarakat dalam melakukan aktivitasnya sehari – hari. Salah satu penyebab terjadinya gangguan sistem tenaga listrik adalah ketidakseimbangan beban yang mempunyai variasi beban listrik yang ada pada industri PT Bonanza Megah. Sifat induktif yang dimiliki beban listrik tersebut dapat menyebabkan rendahnya nilai faktor daya dan nilai jatuh tegangan semakin besar. Untuk meminimalisir hal tersebut dapat dilakukan pemasangan kapasitor bank secara paralel. Tujuan penelitian ini adalah menganalisis pengaruh kapasitor bank terhadap nilai faktor daya dan nilai jatuh tegangan dengan metode perhitungan segitiga daya yang disimulasikan dengan software Etap 19. Sebelum diperbaiki, besar nilai faktor daya (PF) = 0,72 dan nilai jatuh tegangan = 4,31%. Berdasarkan nilai jatuh tegangan tersebut masih tergolong standar karena berdasarkan standar PLN toleransi nilai tegangan adalah +5 dan -10%. Untuk nilai faktor daya minimal adalah 0,85. Akan tetapi nilai faktor daya tergolong tidak standar. Sehubungan dengan hal tersebut PT Bonanza Megah menggunakan kapasitor bank sebesar 6 x 50 kVAR dengan kapasitas kapasitor 4000 F untuk memperbaiki nilai faktor daya dan sekaligus untuk mengurangi nilai jatuh tegangan. Selanjutnya, disimulasikan dengan software Etap 19 dengan cara memasukkan data yang sudah dikumpulkan dan sudah diolah. Setelah dilakukan simulasi dapat dilihat terjadi perubahan nilai jatuh tegangan yang semula 4,31 % menjadi 3,22% dan nilai faktor daya yang semula 0,72 menjadi 0,99. Dari hasil simulasi tersebut nilai faktor daya dan nilai jatuh tegangan menjadi standar/ ideal sesuai standarisasi PLN.Electricity is one of the basic needs of society in carrying out their daily activities. one of the causes of the disturbance of the electric power system is the load imbalance which has a variation of the electrical load that exists in the pt bonanza majestic industry. the inductive nature of the electric load can cause a lower power factor value and a greater voltage drop value. to minimize this, you can install capacitor banks in parallel. the purpose of this study was to analyze the effect of bank capacitors on power factor values and voltage drop values using the power triangle calculation method which was simulated with etap 19 software. before being repaired, the power factor value (pf) = 0.72 and the voltage drop value = 4.31 %. based on the value of the voltage drop, it is still classified as standard because based on pln standards, the tolerance for voltage values is +5 and -10%. for the minimum power factor value is 0.85. however, the power factor value is classified as non-standard. in connection with this, pt bonanza majestic uses a capacitor bank of 6 x 50 kvar with a capacity of 4000 μf capacitor to improve the value of the power factor and at the same time to reduce the value of the voltage drop. then, simulated with etap 19 software by entering data that has been collected and has been processed. after the simulation, it can be seen that there is a change in the value of the voltage drop from 4.31% to 3.22% and the power factor value from 0.72 to 0.99. from the simulation results, the power factor and voltage drop values are standard/ideal according to pln standards.","PeriodicalId":292481,"journal":{"name":"Jambura Journal of Electrical and Electronics Engineering","volume":"40 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2023-07-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Analisis Pengaruh Kapasitor Bank Terhadap Nilai Faktor Daya Dan Nilai Jatuh Tegangan\",\"authors\":\"Bagus Ferdiansah, Agus Margiantono, Fahrudin Ahmad\",\"doi\":\"10.37905/jjeee.v5i2.20893\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Listrik merupakan salah satu kebutuhan pokok masyarakat dalam melakukan aktivitasnya sehari – hari. Salah satu penyebab terjadinya gangguan sistem tenaga listrik adalah ketidakseimbangan beban yang mempunyai variasi beban listrik yang ada pada industri PT Bonanza Megah. Sifat induktif yang dimiliki beban listrik tersebut dapat menyebabkan rendahnya nilai faktor daya dan nilai jatuh tegangan semakin besar. Untuk meminimalisir hal tersebut dapat dilakukan pemasangan kapasitor bank secara paralel. Tujuan penelitian ini adalah menganalisis pengaruh kapasitor bank terhadap nilai faktor daya dan nilai jatuh tegangan dengan metode perhitungan segitiga daya yang disimulasikan dengan software Etap 19. Sebelum diperbaiki, besar nilai faktor daya (PF) = 0,72 dan nilai jatuh tegangan = 4,31%. Berdasarkan nilai jatuh tegangan tersebut masih tergolong standar karena berdasarkan standar PLN toleransi nilai tegangan adalah +5 dan -10%. Untuk nilai faktor daya minimal adalah 0,85. Akan tetapi nilai faktor daya tergolong tidak standar. Sehubungan dengan hal tersebut PT Bonanza Megah menggunakan kapasitor bank sebesar 6 x 50 kVAR dengan kapasitas kapasitor 4000 F untuk memperbaiki nilai faktor daya dan sekaligus untuk mengurangi nilai jatuh tegangan. Selanjutnya, disimulasikan dengan software Etap 19 dengan cara memasukkan data yang sudah dikumpulkan dan sudah diolah. Setelah dilakukan simulasi dapat dilihat terjadi perubahan nilai jatuh tegangan yang semula 4,31 % menjadi 3,22% dan nilai faktor daya yang semula 0,72 menjadi 0,99. Dari hasil simulasi tersebut nilai faktor daya dan nilai jatuh tegangan menjadi standar/ ideal sesuai standarisasi PLN.Electricity is one of the basic needs of society in carrying out their daily activities. one of the causes of the disturbance of the electric power system is the load imbalance which has a variation of the electrical load that exists in the pt bonanza majestic industry. the inductive nature of the electric load can cause a lower power factor value and a greater voltage drop value. to minimize this, you can install capacitor banks in parallel. the purpose of this study was to analyze the effect of bank capacitors on power factor values and voltage drop values using the power triangle calculation method which was simulated with etap 19 software. before being repaired, the power factor value (pf) = 0.72 and the voltage drop value = 4.31 %. based on the value of the voltage drop, it is still classified as standard because based on pln standards, the tolerance for voltage values is +5 and -10%. for the minimum power factor value is 0.85. however, the power factor value is classified as non-standard. in connection with this, pt bonanza majestic uses a capacitor bank of 6 x 50 kvar with a capacity of 4000 μf capacitor to improve the value of the power factor and at the same time to reduce the value of the voltage drop. then, simulated with etap 19 software by entering data that has been collected and has been processed. after the simulation, it can be seen that there is a change in the value of the voltage drop from 4.31% to 3.22% and the power factor value from 0.72 to 0.99. from the simulation results, the power factor and voltage drop values are standard/ideal according to pln standards.\",\"PeriodicalId\":292481,\"journal\":{\"name\":\"Jambura Journal of Electrical and Electronics Engineering\",\"volume\":\"40 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-07-18\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Jambura Journal of Electrical and Electronics Engineering\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.37905/jjeee.v5i2.20893\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Jambura Journal of Electrical and Electronics Engineering","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.37905/jjeee.v5i2.20893","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1
摘要
电力是社区日常活动的基本需求之一。电力系统中断的原因之一是重量失衡,这种失衡在大型PT Bonanza行业中产生了不同程度的电力失衡。电力负荷所具有的内导性会导致功率降低和电压下降增加。为了尽量减少这一点,可以同时安装银行的电容器。本研究的目的是用模拟Etap软件的功率三角计算方法分析银行电容器对电位因子值和电压降值的影响。在纠正之前,功率值(PF) = 0.72,值下降电压= 4.31%。根据降电压值,这仍然是一个标准,因为根据PLN标准,公差为+5和-10%。最小功率值为0.85。然而,功率级的价值是不标准的。在这方面,PT Bonanza华丽地使用了6×50 kVAR的银行电容器,电容容量为4000 F,以修复电容器的价值,同时降低伏电压值。此外,通过输入收集和准备的数据,在Etap软件19中进行模拟。模拟完成后,可以观察到初始电压下降的值4.31 %到3.22%的变化,最初的功率值为0.72到0.99的值。从这些模拟结果中,功率因子值和值下降到符合PLN标准化的标准/理想值。电力是社会在日常活动中最基本的需求之一。电力系统失灵的原因之一是由于不同的电力负荷存在于pt bonanza majestic行业。这种负荷的性质可能是因为低功率因素值和更大的电压下降。为了最小化这个,你可以在平行的银行安装电容器。这项研究的目的是用功率三角计算方法分析银行电容器对值值的影响,该方法与etap 19软件相匹配。在重新计算之前,电源因子值(pf) = 0.72,电压下降= 4.31 %。基于田鼠的价值,它仍然像标准一样机密,因为pln的标准是,voltage收视率是+5和-10%。因为最小的功率系数为0.85。悬浮,能量因子价值是机密的,就像非标准一样。在连接着这个,pt bonanza majestic利用a电容器6 x 50 kvar with a银行capacity of 4000μf电容器to improve功率因子和价值》at the价值》同一时间减少电压下降。然后,输入etap 19软件进行模拟,这些数据一直被收集并一直进行处理。模拟结束后,可以看到计数中有一个变化,从4.31%下降到3.22%,从0.72到0.99的功率因素下降。从结果的模拟中,功率因素和voltage值下降是标准/理想的标准适应的标准。
Analisis Pengaruh Kapasitor Bank Terhadap Nilai Faktor Daya Dan Nilai Jatuh Tegangan
Listrik merupakan salah satu kebutuhan pokok masyarakat dalam melakukan aktivitasnya sehari – hari. Salah satu penyebab terjadinya gangguan sistem tenaga listrik adalah ketidakseimbangan beban yang mempunyai variasi beban listrik yang ada pada industri PT Bonanza Megah. Sifat induktif yang dimiliki beban listrik tersebut dapat menyebabkan rendahnya nilai faktor daya dan nilai jatuh tegangan semakin besar. Untuk meminimalisir hal tersebut dapat dilakukan pemasangan kapasitor bank secara paralel. Tujuan penelitian ini adalah menganalisis pengaruh kapasitor bank terhadap nilai faktor daya dan nilai jatuh tegangan dengan metode perhitungan segitiga daya yang disimulasikan dengan software Etap 19. Sebelum diperbaiki, besar nilai faktor daya (PF) = 0,72 dan nilai jatuh tegangan = 4,31%. Berdasarkan nilai jatuh tegangan tersebut masih tergolong standar karena berdasarkan standar PLN toleransi nilai tegangan adalah +5 dan -10%. Untuk nilai faktor daya minimal adalah 0,85. Akan tetapi nilai faktor daya tergolong tidak standar. Sehubungan dengan hal tersebut PT Bonanza Megah menggunakan kapasitor bank sebesar 6 x 50 kVAR dengan kapasitas kapasitor 4000 F untuk memperbaiki nilai faktor daya dan sekaligus untuk mengurangi nilai jatuh tegangan. Selanjutnya, disimulasikan dengan software Etap 19 dengan cara memasukkan data yang sudah dikumpulkan dan sudah diolah. Setelah dilakukan simulasi dapat dilihat terjadi perubahan nilai jatuh tegangan yang semula 4,31 % menjadi 3,22% dan nilai faktor daya yang semula 0,72 menjadi 0,99. Dari hasil simulasi tersebut nilai faktor daya dan nilai jatuh tegangan menjadi standar/ ideal sesuai standarisasi PLN.Electricity is one of the basic needs of society in carrying out their daily activities. one of the causes of the disturbance of the electric power system is the load imbalance which has a variation of the electrical load that exists in the pt bonanza majestic industry. the inductive nature of the electric load can cause a lower power factor value and a greater voltage drop value. to minimize this, you can install capacitor banks in parallel. the purpose of this study was to analyze the effect of bank capacitors on power factor values and voltage drop values using the power triangle calculation method which was simulated with etap 19 software. before being repaired, the power factor value (pf) = 0.72 and the voltage drop value = 4.31 %. based on the value of the voltage drop, it is still classified as standard because based on pln standards, the tolerance for voltage values is +5 and -10%. for the minimum power factor value is 0.85. however, the power factor value is classified as non-standard. in connection with this, pt bonanza majestic uses a capacitor bank of 6 x 50 kvar with a capacity of 4000 μf capacitor to improve the value of the power factor and at the same time to reduce the value of the voltage drop. then, simulated with etap 19 software by entering data that has been collected and has been processed. after the simulation, it can be seen that there is a change in the value of the voltage drop from 4.31% to 3.22% and the power factor value from 0.72 to 0.99. from the simulation results, the power factor and voltage drop values are standard/ideal according to pln standards.