{"title":"用真实示波器数据再现高阻抗双线对地故障","authors":"W. Heringer, M. D. A. Cordeiro, J. C. H. Paye, A. L. Sousa, A. P. Leão, J. P. A. Vieira, M. C. Santos, G. Cardoso, A. P. de Morais, A. Wontroba, P. E. Farias","doi":"10.1109/TDLA47668.2020.9326209","DOIUrl":null,"url":null,"abstract":"This paper presents the reproduction of an actual high impedance fault (HIF) event of type double line-to-ground using real oscillography data and ATP-EMTP software. The event occured in an overhead distribution system connected to substation Salinópolis 13.8 kV, after two cabes broke and touched a soil contact surface. The reproduction method of the mentioned event is based on simple calculation of fault currents from neutral current measurements to generate the V × I curve used in the HIF model. The results show that current signals obtained from simulation match the current measurements, demonstrating the effectiveness of the proposed method.","PeriodicalId":448644,"journal":{"name":"2020 IEEE PES Transmission & Distribution Conference and Exhibition - Latin America (T&D LA)","volume":"134 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2020-09-28","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Reproduction of a High Impedance Double line-to-ground Fault Using Real Oscillography Data\",\"authors\":\"W. Heringer, M. D. A. Cordeiro, J. C. H. Paye, A. L. Sousa, A. P. Leão, J. P. A. Vieira, M. C. Santos, G. Cardoso, A. P. de Morais, A. Wontroba, P. E. Farias\",\"doi\":\"10.1109/TDLA47668.2020.9326209\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"This paper presents the reproduction of an actual high impedance fault (HIF) event of type double line-to-ground using real oscillography data and ATP-EMTP software. The event occured in an overhead distribution system connected to substation Salinópolis 13.8 kV, after two cabes broke and touched a soil contact surface. The reproduction method of the mentioned event is based on simple calculation of fault currents from neutral current measurements to generate the V × I curve used in the HIF model. The results show that current signals obtained from simulation match the current measurements, demonstrating the effectiveness of the proposed method.\",\"PeriodicalId\":448644,\"journal\":{\"name\":\"2020 IEEE PES Transmission & Distribution Conference and Exhibition - Latin America (T&D LA)\",\"volume\":\"134 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2020-09-28\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2020 IEEE PES Transmission & Distribution Conference and Exhibition - Latin America (T&D LA)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/TDLA47668.2020.9326209\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 IEEE PES Transmission & Distribution Conference and Exhibition - Latin America (T&D LA)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TDLA47668.2020.9326209","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

本文利用实际示波器数据和ATP-EMTP软件再现了实际双线对地高阻抗故障事件。事故发生在连接到Salinópolis 13.8 kV变电站的架空配电系统中,两根电缆断裂并接触到土壤接触面。上述事件的再现方法是基于从中性电流测量中简单计算故障电流,以生成HIF模型中使用的V × I曲线。结果表明,仿真得到的电流信号与电流测量值吻合,验证了所提方法的有效性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Reproduction of a High Impedance Double line-to-ground Fault Using Real Oscillography Data
This paper presents the reproduction of an actual high impedance fault (HIF) event of type double line-to-ground using real oscillography data and ATP-EMTP software. The event occured in an overhead distribution system connected to substation Salinópolis 13.8 kV, after two cabes broke and touched a soil contact surface. The reproduction method of the mentioned event is based on simple calculation of fault currents from neutral current measurements to generate the V × I curve used in the HIF model. The results show that current signals obtained from simulation match the current measurements, demonstrating the effectiveness of the proposed method.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信