{"title":"避雷器连接线电感抗压降的估计","authors":"Y. Trotsenko, Artem Nesterko, V. Chyzhevskyi, M. Dixit","doi":"10.30929/1995-0519.2021.4.157-162","DOIUrl":null,"url":null,"abstract":"Purpose. The results of studying the voltage drop in the inductive ractance of the connecting wires of surge arresters installed in open switchgear are presented. Methodology. Free software for circuit simulation was used to solve electri- cal circuits with nonlinear parameters. To take into account the differences between the negative and positive lightning current impulses, the oscillograms of real lightning currents were digitized using free specialized software. Results. The duration of the impulse front (as well as the total impulse duration) of the positive lightning significantly exceeds the corresponding parameters of the negative lightning current, so the charge carried by the positive lightning significantly exceeds the charge carried by the negative lightning. For these reasons, positive lightning, although less common than ЕЛЕКТРОЕНЕРГЕТИКА, ЕЛЕКТРОТЕХНІКА ТА ЕЛЕКТРОМЕХАНІКА Вісник КрНУ імені Михайла Остроградського. Випуск 4/2021 (129) 162 negative lightning, is more dangerous. It is found that due to the slower front of the impulse, the voltage drop in induc- tive reactance of connecting wires of the surge arresters in the case of positive lightning in 8-11 times less than in the case of negative lightning. Analytical formulas for calculating the inductance of the connecting wires, which take into account the geometric dimensions of the wires, provide more accurate results than the average inductance value of 1.3 μH/m given in the literature. Originality. The approach takes into account the differences between impulses of light- ning currents of negative and positive polarity, which cannot be achieved with use of the approximation of lightning currents by simplified mathematical expressions. Practical value. It is found that voltage drops in the inductive reac- tance will be more dangerous in case of long wire lengths and negative lightning current impulses with a steep front. Conclusions. Further development of the proposed approach is seen in its use for the analysis of circuits for protection of electrical equipment of high-voltage electrical networks from lightning overvoltages using surge arresters. Refer- ences 15, figures 10.","PeriodicalId":405654,"journal":{"name":"Transactions of Kremenchuk Mykhailo Ostrohradskyi National University","volume":"17 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-08-23","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"ESTIMATION OF VOLTAGE DROP IN INDUCTIVE REACTANCE OF CONNECTING WIRES OF SURGE ARRESTERS\",\"authors\":\"Y. Trotsenko, Artem Nesterko, V. Chyzhevskyi, M. Dixit\",\"doi\":\"10.30929/1995-0519.2021.4.157-162\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Purpose. The results of studying the voltage drop in the inductive ractance of the connecting wires of surge arresters installed in open switchgear are presented. Methodology. Free software for circuit simulation was used to solve electri- cal circuits with nonlinear parameters. To take into account the differences between the negative and positive lightning current impulses, the oscillograms of real lightning currents were digitized using free specialized software. Results. The duration of the impulse front (as well as the total impulse duration) of the positive lightning significantly exceeds the corresponding parameters of the negative lightning current, so the charge carried by the positive lightning significantly exceeds the charge carried by the negative lightning. For these reasons, positive lightning, although less common than ЕЛЕКТРОЕНЕРГЕТИКА, ЕЛЕКТРОТЕХНІКА ТА ЕЛЕКТРОМЕХАНІКА Вісник КрНУ імені Михайла Остроградського. Випуск 4/2021 (129) 162 negative lightning, is more dangerous. It is found that due to the slower front of the impulse, the voltage drop in induc- tive reactance of connecting wires of the surge arresters in the case of positive lightning in 8-11 times less than in the case of negative lightning. Analytical formulas for calculating the inductance of the connecting wires, which take into account the geometric dimensions of the wires, provide more accurate results than the average inductance value of 1.3 μH/m given in the literature. Originality. The approach takes into account the differences between impulses of light- ning currents of negative and positive polarity, which cannot be achieved with use of the approximation of lightning currents by simplified mathematical expressions. Practical value. It is found that voltage drops in the inductive reac- tance will be more dangerous in case of long wire lengths and negative lightning current impulses with a steep front. Conclusions. Further development of the proposed approach is seen in its use for the analysis of circuits for protection of electrical equipment of high-voltage electrical networks from lightning overvoltages using surge arresters. Refer- ences 15, figures 10.\",\"PeriodicalId\":405654,\"journal\":{\"name\":\"Transactions of Kremenchuk Mykhailo Ostrohradskyi National University\",\"volume\":\"17 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2021-08-23\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Transactions of Kremenchuk Mykhailo Ostrohradskyi National University\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.30929/1995-0519.2021.4.157-162\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Transactions of Kremenchuk Mykhailo Ostrohradskyi National University","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.30929/1995-0519.2021.4.157-162","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

目的。本文介绍了开路式开关柜避雷器接线电感电阻压降的研究结果。方法。利用免费的电路仿真软件求解具有非线性参数的电路。考虑到正负雷电电流脉冲的差异,利用免费的专业软件对真实雷电电流的波形图进行了数字化处理。结果。正极闪电的脉冲锋持续时间(以及总脉冲持续时间)明显超过负极闪电电流的相应参数,因此正极闪电所携带的电荷明显超过负极闪电所携带的电荷。由于这些原因,积极的闪电,虽然普遍低于ЕЛЕКТРОЕНЕРГЕТИКА,ЕЛЕКТРОТЕХНІКАТАЕЛЕКТРОМЕХАНІКАВісникКрНУіменіМихайлаОстроградського。Випуск 4/2021(129) 162负闪电,更危险。研究发现,由于脉冲前端较慢,在正极雷击情况下避雷器接线的感抗压降比在负极雷击情况下小8 ~ 11倍。计算连接导线电感的解析公式考虑了导线的几何尺寸,比文献中给出的平均电感值1.3 μH/m更为精确。创意。该方法考虑了雷电电流的正负极性脉冲之间的差异,这是用简化的数学表达式近似雷电电流所不能达到的。实用价值。研究发现,在导线长度较长和锋面较陡的负雷击电流脉冲情况下,电感抗电压降更危险。结论。所提出的方法的进一步发展可以在使用避雷器保护高压电网电气设备免受雷电过电压的电路分析中看到。参考文献15,图10。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
ESTIMATION OF VOLTAGE DROP IN INDUCTIVE REACTANCE OF CONNECTING WIRES OF SURGE ARRESTERS
Purpose. The results of studying the voltage drop in the inductive ractance of the connecting wires of surge arresters installed in open switchgear are presented. Methodology. Free software for circuit simulation was used to solve electri- cal circuits with nonlinear parameters. To take into account the differences between the negative and positive lightning current impulses, the oscillograms of real lightning currents were digitized using free specialized software. Results. The duration of the impulse front (as well as the total impulse duration) of the positive lightning significantly exceeds the corresponding parameters of the negative lightning current, so the charge carried by the positive lightning significantly exceeds the charge carried by the negative lightning. For these reasons, positive lightning, although less common than ЕЛЕКТРОЕНЕРГЕТИКА, ЕЛЕКТРОТЕХНІКА ТА ЕЛЕКТРОМЕХАНІКА Вісник КрНУ імені Михайла Остроградського. Випуск 4/2021 (129) 162 negative lightning, is more dangerous. It is found that due to the slower front of the impulse, the voltage drop in induc- tive reactance of connecting wires of the surge arresters in the case of positive lightning in 8-11 times less than in the case of negative lightning. Analytical formulas for calculating the inductance of the connecting wires, which take into account the geometric dimensions of the wires, provide more accurate results than the average inductance value of 1.3 μH/m given in the literature. Originality. The approach takes into account the differences between impulses of light- ning currents of negative and positive polarity, which cannot be achieved with use of the approximation of lightning currents by simplified mathematical expressions. Practical value. It is found that voltage drops in the inductive reac- tance will be more dangerous in case of long wire lengths and negative lightning current impulses with a steep front. Conclusions. Further development of the proposed approach is seen in its use for the analysis of circuits for protection of electrical equipment of high-voltage electrical networks from lightning overvoltages using surge arresters. Refer- ences 15, figures 10.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信