{"title":"An experimental Investigation of effectiveness of a closed-end flat heat pipe heat exchanger (CEFHPHE)","authors":"W. Srimuang, P. Khantikomol, B. Krittacom","doi":"10.5481/KKUENJ.2013.40.1.3","DOIUrl":null,"url":null,"abstract":"The effectiveness of a closed-end flat heat pipe heat exchanger (CEFHPHE) was investigated experimentally. The CEFHPHE consists of three parts, which include the evaporator, adiabatic and condenser sections that the lengths were 300, 100 and 300 mm respectively. The standard copper tube with inner diameter of 8.6 mm and 0.46 mm thick was pressed to reform its cross sectional area for a flat tube, and then bent to many U-shapes, which was closed at both ends. The water was used for working fluid with filling ratios of 45% of internal volume. In experiments, hot air was used for supplying the heat to the evaporator section with different temperatures (105-145oC), and different velocities (0.5-2.0 m/s). Fresh air was used for cooling condenser section with temperature approximately 30oC, and was kept constant velocity at 0.5 m/s. The experimental results indicated that the effectiveness of CEFHPHE increase with the inlet hot air temperature, and decrease with the increase of hot air velocity. In addition, the effectiveness of the CEFHPHE obtained from the experiments varied between 0.35 and 0.74.","PeriodicalId":37310,"journal":{"name":"Engineering and Applied Science Research","volume":"40 1","pages":"21-27"},"PeriodicalIF":0.0000,"publicationDate":"2013-05-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Engineering and Applied Science Research","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.5481/KKUENJ.2013.40.1.3","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"Engineering","Score":null,"Total":0}
引用次数: 1
Abstract
The effectiveness of a closed-end flat heat pipe heat exchanger (CEFHPHE) was investigated experimentally. The CEFHPHE consists of three parts, which include the evaporator, adiabatic and condenser sections that the lengths were 300, 100 and 300 mm respectively. The standard copper tube with inner diameter of 8.6 mm and 0.46 mm thick was pressed to reform its cross sectional area for a flat tube, and then bent to many U-shapes, which was closed at both ends. The water was used for working fluid with filling ratios of 45% of internal volume. In experiments, hot air was used for supplying the heat to the evaporator section with different temperatures (105-145oC), and different velocities (0.5-2.0 m/s). Fresh air was used for cooling condenser section with temperature approximately 30oC, and was kept constant velocity at 0.5 m/s. The experimental results indicated that the effectiveness of CEFHPHE increase with the inlet hot air temperature, and decrease with the increase of hot air velocity. In addition, the effectiveness of the CEFHPHE obtained from the experiments varied between 0.35 and 0.74.
期刊介绍:
Publication of the journal started in 1974. Its original name was “KKU Engineering Journal”. English and Thai manuscripts were accepted. The journal was originally aimed at publishing research that was conducted and implemented in the northeast of Thailand. It is regarded a national journal and has been indexed in the Thai-journal Citation Index (TCI) database since 2004. The journal now accepts only English language manuscripts and became open-access in 2015 to attract more international readers. It was renamed Engineering and Applied Science Research in 2017. The editorial team agreed to publish more international papers, therefore, the new journal title is more appropriate. The journal focuses on research in the field of engineering that not only presents highly original ideas and advanced technology, but also are practical applications of appropriate technology.