STUDI KONDISI MINYAK TRANSFORMATOR DAYA BERDASARKAN HASIL UJI DISSOLVED GAS ANALYSIS (DGA) DENGAN METODE TOTAL DISSOLVED COMBUSTIBLE GAS (TDCG) DAN METODE KEY GAS DI PT.INDONESIA POWER PLTU PANGKALAN SUSU
Rahmadani Pardede, Ezwarsyah Ezwarsyah, K. Kartika, Asran Asran
{"title":"STUDI KONDISI MINYAK TRANSFORMATOR DAYA BERDASARKAN HASIL UJI DISSOLVED GAS ANALYSIS (DGA) DENGAN METODE TOTAL DISSOLVED COMBUSTIBLE GAS (TDCG) DAN METODE KEY GAS DI PT.INDONESIA POWER PLTU PANGKALAN SUSU","authors":"Rahmadani Pardede, Ezwarsyah Ezwarsyah, K. Kartika, Asran Asran","doi":"10.29103/jee.v12i2.13519","DOIUrl":null,"url":null,"abstract":"2023 dilakukan pengujian DGA ( Dissolved Gas Analysis ) pada transformator unit 2 dan unit 3. Hasil TDCG (Total Dissolved Combustible Gas ) unit 2 562 ppm dan dalam kondisi 1 dengan intepretasi bahwa transformator dapat beroperasi dengan normal, tapi harus waspada kenaikan suhu minyak transformator. Hasil TDCG ( Total Dissolved Combustible Gas ) unit 3 122 ppm dalam kondisi 1 dengan intepretasi bahwa transformator dapat beroperasi dengan normal tapi harus waspada kenaikan susu minyak transformator. Metode TDCG ( Total Dissolved Combustible Gas ) adalah penjumlahan gas terlarut atau fault gas. Metode key gas adalah mendeteksi kegagalan pada minyak transformator. Untuk menjaga kualitas minyak transformator di PT. Indonesia Power PLTU Pangkalan Susu dilakukan pengujian rutin 3 bulan sekali.","PeriodicalId":220025,"journal":{"name":"Jurnal Energi Elektrik","volume":"1 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2023-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Jurnal Energi Elektrik","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.29103/jee.v12i2.13519","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
2023 dilakukan pengujian DGA ( Dissolved Gas Analysis ) pada transformator unit 2 dan unit 3. Hasil TDCG (Total Dissolved Combustible Gas ) unit 2 562 ppm dan dalam kondisi 1 dengan intepretasi bahwa transformator dapat beroperasi dengan normal, tapi harus waspada kenaikan suhu minyak transformator. Hasil TDCG ( Total Dissolved Combustible Gas ) unit 3 122 ppm dalam kondisi 1 dengan intepretasi bahwa transformator dapat beroperasi dengan normal tapi harus waspada kenaikan susu minyak transformator. Metode TDCG ( Total Dissolved Combustible Gas ) adalah penjumlahan gas terlarut atau fault gas. Metode key gas adalah mendeteksi kegagalan pada minyak transformator. Untuk menjaga kualitas minyak transformator di PT. Indonesia Power PLTU Pangkalan Susu dilakukan pengujian rutin 3 bulan sekali.