Miroslav Gutten, Daniel Korenciak, Martin Karman, Peter Brncal, Matej Kucera, Tomasz N. Koltunowicz, Maciej Sulowicz
{"title":"Combination of Non-contact and Contact Measuring Methods for Analyzing Structural Conditions of Dry Transformers","authors":"Miroslav Gutten, Daniel Korenciak, Martin Karman, Peter Brncal, Matej Kucera, Tomasz N. Koltunowicz, Maciej Sulowicz","doi":"10.2478/msr-2023-0020","DOIUrl":null,"url":null,"abstract":"Abstract The article describes the non-contact and contact analysis of 1-MVA dry power transformers with epoxy-resin insulation using an acoustic camera and frequency analyzer with automatic sweeping for low-middle frequency areas. Power transformers are most commonly used for construction component (core, windings, taps) analysis. The electrical, non-rotating machine generates electromagnetic and acoustic emissions that can be used to analyze dry transformers during their operation. Non-contact online diagnostic methods have many advantages over offline methods because it is not necessary to shut down the transformer, and also, the condition and behaviour of the machine are analyzed during its normal operation. The article presents the analysis and comparison of structural parts of the distribution dry transformers of the same type and power. The problem of insufficient or incorrect clamp-screw connection was identified using the SFRA (Sweep Frequency Response Analysis) method.","PeriodicalId":49848,"journal":{"name":"Measurement Science Review","volume":"36 1","pages":"0"},"PeriodicalIF":1.0000,"publicationDate":"2023-08-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Measurement Science Review","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.2478/msr-2023-0020","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q4","JCRName":"INSTRUMENTS & INSTRUMENTATION","Score":null,"Total":0}
引用次数: 0
Abstract
Abstract The article describes the non-contact and contact analysis of 1-MVA dry power transformers with epoxy-resin insulation using an acoustic camera and frequency analyzer with automatic sweeping for low-middle frequency areas. Power transformers are most commonly used for construction component (core, windings, taps) analysis. The electrical, non-rotating machine generates electromagnetic and acoustic emissions that can be used to analyze dry transformers during their operation. Non-contact online diagnostic methods have many advantages over offline methods because it is not necessary to shut down the transformer, and also, the condition and behaviour of the machine are analyzed during its normal operation. The article presents the analysis and comparison of structural parts of the distribution dry transformers of the same type and power. The problem of insufficient or incorrect clamp-screw connection was identified using the SFRA (Sweep Frequency Response Analysis) method.
期刊介绍:
- theory of measurement - mathematical processing of measured data - measurement uncertainty minimisation - statistical methods in data evaluation and modelling - measurement as an interdisciplinary activity - measurement science in education - medical imaging methods, image processing - biosignal measurement, processing and analysis - model based biomeasurements - neural networks in biomeasurement - telemeasurement in biomedicine - measurement in nanomedicine - measurement of basic physical quantities - magnetic and electric fields measurements - measurement of geometrical and mechanical quantities - optical measuring methods - electromagnetic compatibility - measurement in material science