{"title":"Real-time measurement of power quantities under sinusoidal and non-sinusoidal conditions for single-phase systems","authors":"H. Dalvand, V. Agelidis","doi":"10.1109/ECCE.2010.5617997","DOIUrl":null,"url":null,"abstract":"This paper describes the real-time implementation of a time-domain method to calculate the power quantities based on IEEE 1459-2000 for single-phase systems under sinusoidal and non-sinusoidal conditions. The proposed method is based on recursive implementation of Park transformations for the detection of fundamental and harmonic components of voltage and current. The technique employs a recursive algorithm that avoids the low-pass filtering stage which causes uncertainty and delay in the conventional Park transformation based approaches making real-time measuring of the quantities possible with very good accuracy and reduced delay. The performance of the method is confirmed by simulated using MATLAB/SIMULINK and selected results are presented. Moreover, the proposed technique is implemented on a PC-based instrument in order to investigate its accuracy in the presence of measurement transducers.","PeriodicalId":161915,"journal":{"name":"2010 IEEE Energy Conversion Congress and Exposition","volume":"10 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2010-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2010 IEEE Energy Conversion Congress and Exposition","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ECCE.2010.5617997","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2
Abstract
This paper describes the real-time implementation of a time-domain method to calculate the power quantities based on IEEE 1459-2000 for single-phase systems under sinusoidal and non-sinusoidal conditions. The proposed method is based on recursive implementation of Park transformations for the detection of fundamental and harmonic components of voltage and current. The technique employs a recursive algorithm that avoids the low-pass filtering stage which causes uncertainty and delay in the conventional Park transformation based approaches making real-time measuring of the quantities possible with very good accuracy and reduced delay. The performance of the method is confirmed by simulated using MATLAB/SIMULINK and selected results are presented. Moreover, the proposed technique is implemented on a PC-based instrument in order to investigate its accuracy in the presence of measurement transducers.