{"title":"The flashover voltage characteristic comparative analysis of the anti contaminant equipment","authors":"Yong-Up Park, T. Kwon, D. Ra","doi":"10.1109/ISEIM.2008.4664438","DOIUrl":null,"url":null,"abstract":"We carried out the dry flashover test and wet flashover test, after the artificial contaminant damage work, in order to inspect the validness of the anti contaminant equipment as a suspension insulator (ceramic material, EPDM), LP insulator, arrester and COS. As a result of experiment, the dry flashover voltage value of the damaged equipment with the salinity was similar to the normal equipment even if the equipment is damaged with the salinity. But when the humidity was high under the damaged state, the flashover voltage value of some distribution equipment was low under the 20 kV.","PeriodicalId":158811,"journal":{"name":"2008 International Symposium on Electrical Insulating Materials (ISEIM 2008)","volume":"115 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2008-10-31","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2008 International Symposium on Electrical Insulating Materials (ISEIM 2008)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ISEIM.2008.4664438","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
We carried out the dry flashover test and wet flashover test, after the artificial contaminant damage work, in order to inspect the validness of the anti contaminant equipment as a suspension insulator (ceramic material, EPDM), LP insulator, arrester and COS. As a result of experiment, the dry flashover voltage value of the damaged equipment with the salinity was similar to the normal equipment even if the equipment is damaged with the salinity. But when the humidity was high under the damaged state, the flashover voltage value of some distribution equipment was low under the 20 kV.