{"title":"Breakdowns of vacuum interrupters behind front of a lightning impulse","authors":"L. Rylskaya","doi":"10.1109/DEIV.2012.6412453","DOIUrl":null,"url":null,"abstract":"Laws of occurrence of breakdowns of vacuum interrupters behind front of a lightning impulse at recession of voltage (overdue delayed breakdowns) are experimentally investigated and the hypothesis of their nature is developed. It is shown, that the reason of breakdowns is the high-voltage discharge on an internal surface of insulating cases of vacuum interrupter.","PeriodicalId":130964,"journal":{"name":"2012 25th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV)","volume":"364 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2012-09-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2012 25th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/DEIV.2012.6412453","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
Laws of occurrence of breakdowns of vacuum interrupters behind front of a lightning impulse at recession of voltage (overdue delayed breakdowns) are experimentally investigated and the hypothesis of their nature is developed. It is shown, that the reason of breakdowns is the high-voltage discharge on an internal surface of insulating cases of vacuum interrupter.