{"title":"A fork connected auto-transformer based 24-pulse AC-DC converter","authors":"B. Singh, S. Gairola","doi":"10.1109/IICPE.2006.4685364","DOIUrl":null,"url":null,"abstract":"In this paper, a 24-pulse AC-DC converter is designed, modeled and simulated to feed non-isolated industrial loads. The proposed configuration consists of an auto-transformer based on fork connection to overcome current harmonic problems in AC mains. It improves power quality at AC mains and it meets IEEE-519 standard requirements at varying loads. A set of power quality indices on input AC mains and on DC bus for a load fed from 6-pulse and 12-pulse AC-DC converters is also given to compare their performance. It is observed that input current total harmonic distortion (THD) of less than 5% is possible with the proposed topology of AC-DC converter at varying loads.","PeriodicalId":227812,"journal":{"name":"2006 India International Conference on Power Electronics","volume":"182 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-12-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"5","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2006 India International Conference on Power Electronics","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/IICPE.2006.4685364","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 5
Abstract
In this paper, a 24-pulse AC-DC converter is designed, modeled and simulated to feed non-isolated industrial loads. The proposed configuration consists of an auto-transformer based on fork connection to overcome current harmonic problems in AC mains. It improves power quality at AC mains and it meets IEEE-519 standard requirements at varying loads. A set of power quality indices on input AC mains and on DC bus for a load fed from 6-pulse and 12-pulse AC-DC converters is also given to compare their performance. It is observed that input current total harmonic distortion (THD) of less than 5% is possible with the proposed topology of AC-DC converter at varying loads.