Two application case studies of short switchboards in obstructed electrical rooms

K. Clemente
{"title":"Two application case studies of short switchboards in obstructed electrical rooms","authors":"K. Clemente","doi":"10.1109/ICPS.2018.8369991","DOIUrl":null,"url":null,"abstract":"A hotel switchboard located in an attached below-grade garage was corroded at its base from water entering through the building wall during extended, high-volume rainfall events. The owner requested replacement of the 35-year-old switchboard to correct several issues, even though several efforts to stop water ingress were not successful. Elevation of the replacement switchboard to guard from contact with rainwater ingress was at first thought infeasible due to low deck-to-deck height in the parking garage. An alternate construction switchboard of shorter height was specified to permit elevation of a replacement switchboard at the original location. An office building interior was thoroughly renovated, with emphasis on flooding resiliency for ground-floor elements including a service switchboard. Sandbags at exterior doors and other evidence of occasional minor flooding of the ground floor emphasized the need for design measures to protect equipment. The electrical room floor-to-ceiling height was only 8′0″, leaving little room for device elevation beyond a standard concrete housekeeping pad. An alternate construction switchboard of shorter height was specified to permit an 18″ elevation in the original location. Overhead working space was retained for use in routing feeder conduits.","PeriodicalId":142445,"journal":{"name":"2018 IEEE/IAS 54th Industrial and Commercial Power Systems Technical Conference (I&CPS)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2018-05-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 IEEE/IAS 54th Industrial and Commercial Power Systems Technical Conference (I&CPS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICPS.2018.8369991","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

A hotel switchboard located in an attached below-grade garage was corroded at its base from water entering through the building wall during extended, high-volume rainfall events. The owner requested replacement of the 35-year-old switchboard to correct several issues, even though several efforts to stop water ingress were not successful. Elevation of the replacement switchboard to guard from contact with rainwater ingress was at first thought infeasible due to low deck-to-deck height in the parking garage. An alternate construction switchboard of shorter height was specified to permit elevation of a replacement switchboard at the original location. An office building interior was thoroughly renovated, with emphasis on flooding resiliency for ground-floor elements including a service switchboard. Sandbags at exterior doors and other evidence of occasional minor flooding of the ground floor emphasized the need for design measures to protect equipment. The electrical room floor-to-ceiling height was only 8′0″, leaving little room for device elevation beyond a standard concrete housekeeping pad. An alternate construction switchboard of shorter height was specified to permit an 18″ elevation in the original location. Overhead working space was retained for use in routing feeder conduits.
短路配电板在封闭电气室内的两个应用案例研究
酒店配电盘位于附属的地下车库,在长时间的高降雨量事件中,水通过建筑墙壁进入其底部,导致其腐蚀。业主要求更换已有35年历史的配电板,以纠正几个问题,尽管几次阻止进水的努力都没有成功。由于停车场甲板与甲板之间的高度较低,更换配电板的标高最初被认为是不可行的。指定了一种较矮的备用结构配电盘,以便在原位置安装替换配电盘。办公楼的内部进行了彻底的翻新,重点是一楼元素的抗洪能力,包括服务配电盘。室外门上的沙袋和地面层偶尔发生的轻微洪水的其他证据强调了保护设备的设计措施的必要性。电气室的地板到天花板的高度只有8英尺″,除了一个标准的混凝土清洁垫,留给设备高度的空间很小。指定了一个较短高度的替代结构配电板,以允许在原始位置的18″标高。保留架空工作空间,用于布线馈线管道。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信