Sishui No.2 Main Transformer Winding Fault Analysis

Yanhai Huang, T. Hai, Chenghao Lan, Jia-sen Zhu, Zhitong Liu, Yanjun Pang
{"title":"Sishui No.2 Main Transformer Winding Fault Analysis","authors":"Yanhai Huang, T. Hai, Chenghao Lan, Jia-sen Zhu, Zhitong Liu, Yanjun Pang","doi":"10.1109/CICED.2018.8592508","DOIUrl":null,"url":null,"abstract":"Transformer Winding Fault is one of the main causes of Transformer damage. When a transformer has an outlet short-circuit accident, it flows through a large short circuit current in the transformer winding. The short circuit current generates electrodynamic force under the mutual action of the leakage magnetic field and can lead to failure of the transformer winding. Based on the analysis of the short circuit accident at the outlet of the No.2 main transformer in Sishui substation, it is very effective to judge transformer winding fault by combining the frequency response method of transformer windings with chromatographic analysis. In order to avoid the override trip accident, the cable should be changed to a fast fuse cabinet or a set of drop switches. In order to avoid the short circuit damage to the transformer, the manufacturer is required to provide the test report on the short circuit resistance of the transformer.","PeriodicalId":142885,"journal":{"name":"2018 China International Conference on Electricity Distribution (CICED)","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2018-09-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 China International Conference on Electricity Distribution (CICED)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CICED.2018.8592508","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Transformer Winding Fault is one of the main causes of Transformer damage. When a transformer has an outlet short-circuit accident, it flows through a large short circuit current in the transformer winding. The short circuit current generates electrodynamic force under the mutual action of the leakage magnetic field and can lead to failure of the transformer winding. Based on the analysis of the short circuit accident at the outlet of the No.2 main transformer in Sishui substation, it is very effective to judge transformer winding fault by combining the frequency response method of transformer windings with chromatographic analysis. In order to avoid the override trip accident, the cable should be changed to a fast fuse cabinet or a set of drop switches. In order to avoid the short circuit damage to the transformer, the manufacturer is required to provide the test report on the short circuit resistance of the transformer.
泗水2号主变压器绕组故障分析
变压器绕组故障是变压器损坏的主要原因之一。当变压器发生出口短路事故时,会在变压器绕组中流过较大的短路电流。短路电流在漏磁场的相互作用下产生电动力,可导致变压器绕组失效。通过对泗水变电站2号主变压器出口短路事故的分析,将变压器绕组频率响应法与色谱分析法相结合,对变压器绕组故障进行判断是非常有效的。为避免超驰跳闸事故,电缆应改为快速熔丝柜或一组跌落开关。为避免变压器短路损坏,要求生产厂家提供变压器短路电阻的试验报告。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信