{"title":"A novel method for single phase-to-ground fault location based on wavelet analysis and correlation","authors":"T. Bi, Rongrong Shen, J. Plans, Huashi Zhao","doi":"10.1109/ISGT.2013.6497876","DOIUrl":null,"url":null,"abstract":"This paper deals with the problem of single phase-to-ground fault location in distribution networks. A novel method is proposed that overcomes the difficulties that traditional fault location methods have, like their sensibility to the large transition resistance due to the fault. First, correlation is used in combination with the wavelet transform to analyze the series of transient electric wavefronts generated by the fault. Then, the travelling wave principle is applied to determine the distance between the busbar and the fault location. Theory analysis and ATP simulation indicate that the proposed method is robust and accurate.","PeriodicalId":268687,"journal":{"name":"2013 IEEE PES Innovative Smart Grid Technologies Conference (ISGT)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2013-04-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"8","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2013 IEEE PES Innovative Smart Grid Technologies Conference (ISGT)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ISGT.2013.6497876","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 8
Abstract
This paper deals with the problem of single phase-to-ground fault location in distribution networks. A novel method is proposed that overcomes the difficulties that traditional fault location methods have, like their sensibility to the large transition resistance due to the fault. First, correlation is used in combination with the wavelet transform to analyze the series of transient electric wavefronts generated by the fault. Then, the travelling wave principle is applied to determine the distance between the busbar and the fault location. Theory analysis and ATP simulation indicate that the proposed method is robust and accurate.