Reduction of harmonic pollution in distribution networks

W. Lawrance, G. Michalik, W. Mielczarski, J. Szczepanik
{"title":"Reduction of harmonic pollution in distribution networks","authors":"W. Lawrance, G. Michalik, W. Mielczarski, J. Szczepanik","doi":"10.1109/EMPD.1995.500725","DOIUrl":null,"url":null,"abstract":"The paper presents two new schemes of harmonic current reduction in distribution circuits. The first scheme aims at the reduction of harmonics generated by six pulse bridge rectifiers which are common nonlinear loads in industry. The new approach is based on injection of the third harmonic current into the transformer secondary. The current injected is generated in two passive filters connected between the outputs of the bridge and the common point of transformer secondary. The scheme is very effective, reducing harmonic distortion in the supply current from 27% to 4-5%. The second scheme presented aims at the reduction of harmonic distortion caused by fluorescent lamp systems. It assumes the installation of a series filter in the neutral conductor. A specially designed filter provides a low impedance path for the first harmonic current and high impedance for higher harmonics. Simulation and laboratory tests show significant reduction of harmonics in the neutral and phase conductors.","PeriodicalId":447674,"journal":{"name":"Proceedings 1995 International Conference on Energy Management and Power Delivery EMPD '95","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1995-11-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"6","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Proceedings 1995 International Conference on Energy Management and Power Delivery EMPD '95","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/EMPD.1995.500725","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 6

Abstract

The paper presents two new schemes of harmonic current reduction in distribution circuits. The first scheme aims at the reduction of harmonics generated by six pulse bridge rectifiers which are common nonlinear loads in industry. The new approach is based on injection of the third harmonic current into the transformer secondary. The current injected is generated in two passive filters connected between the outputs of the bridge and the common point of transformer secondary. The scheme is very effective, reducing harmonic distortion in the supply current from 27% to 4-5%. The second scheme presented aims at the reduction of harmonic distortion caused by fluorescent lamp systems. It assumes the installation of a series filter in the neutral conductor. A specially designed filter provides a low impedance path for the first harmonic current and high impedance for higher harmonics. Simulation and laboratory tests show significant reduction of harmonics in the neutral and phase conductors.
减少配电网的谐波污染
本文提出了两种新的配电回路谐波电流抑制方案。第一种方案旨在降低六个脉冲桥式整流器产生的谐波,这是工业中常见的非线性负载。新方法是将三次谐波电流注入变压器二次变压器中。注入电流由连接在桥的输出和变压器二次共点之间的两个无源滤波器产生。该方案非常有效,将电源电流中的谐波失真从27%降低到4-5%。提出的第二个方案旨在减少由荧光灯系统引起的谐波失真。它假定在中性导体中安装了串联滤波器。特殊设计的滤波器为第一次谐波电流提供低阻抗路径,为更高次谐波电流提供高阻抗路径。模拟和实验室测试表明,在中性和相导体谐波显著降低。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信