Case study of ANSI standard delta-wye distribution transformer

M. T. Al-Hajri
{"title":"Case study of ANSI standard delta-wye distribution transformer","authors":"M. T. Al-Hajri","doi":"10.1109/ELINSL.2006.1665293","DOIUrl":null,"url":null,"abstract":"An over current relay (51N) of a distribution feeder that feeds a branchy overhead line failed to eliminate a fault, which resulted from a fallen conductor at the primary side of the delta-wye distribution transformer. This was linked to the earth's high resistance. In the first part of this paper, the aforementioned reason will be proven to be not credible and that the load-side fallen conductor resulted in a very small return current that cannot be detected. In the second part of this paper, the fact that the voltage will build up at the distribution transformer primary side in case the transformer has a primary single phase blown fuse and unbalance loads will be presented","PeriodicalId":427638,"journal":{"name":"Conference Record of the 2006 IEEE International Symposium on Electrical Insulation","volume":"201 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-06-11","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Conference Record of the 2006 IEEE International Symposium on Electrical Insulation","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ELINSL.2006.1665293","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

An over current relay (51N) of a distribution feeder that feeds a branchy overhead line failed to eliminate a fault, which resulted from a fallen conductor at the primary side of the delta-wye distribution transformer. This was linked to the earth's high resistance. In the first part of this paper, the aforementioned reason will be proven to be not credible and that the load-side fallen conductor resulted in a very small return current that cannot be detected. In the second part of this paper, the fact that the voltage will build up at the distribution transformer primary side in case the transformer has a primary single phase blown fuse and unbalance loads will be presented
ANSI标准三角型配电变压器实例分析
为支路架空线路供电的配电馈线的过电流继电器(51N)未能消除故障,该故障是由三角形配电变压器主侧导体脱落引起的。这与地球的高电阻有关。在本文的第一部分,将证明上述原因是不可信的,负载侧的跌落导体导致了一个非常小的回电流,无法检测到。在本文的第二部分,电压将建立在配电变压器初级侧的事实,如果变压器有一个初级单相熔断器熔断和不平衡负载将被提出
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信