{"title":"A method for calibration of partial discharge calibrators","authors":"O. Gunnarsson, A. Bergman, K. Rydler","doi":"10.1109/CPEM.1998.699868","DOIUrl":null,"url":null,"abstract":"A method for calibration of partial discharge calibrators has been developed based on passive integration of the induced charge. The voltage over a known capacitor is measured by a calibrated digital sampling voltmeter and the charge is calculated as the voltage multiplied by the capacitance. The best achieved uncertainty is /spl plusmn/2% for a coverage factor k=2.","PeriodicalId":239228,"journal":{"name":"1998 Conference on Precision Electromagnetic Measurements Digest (Cat. No.98CH36254)","volume":"46 3 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1998-07-06","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"16","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"1998 Conference on Precision Electromagnetic Measurements Digest (Cat. No.98CH36254)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CPEM.1998.699868","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 16
Abstract
A method for calibration of partial discharge calibrators has been developed based on passive integration of the induced charge. The voltage over a known capacitor is measured by a calibrated digital sampling voltmeter and the charge is calculated as the voltage multiplied by the capacitance. The best achieved uncertainty is /spl plusmn/2% for a coverage factor k=2.