Analysis on the malfunction of zero sequence protection in 35kV ungrounded system of wind farm

Liu Zhi-qiang, Liu Wei-ming, Chen Xiao-lu, Liu Chun-Hui, Bai Yun-Peng, Xu Cai
{"title":"Analysis on the malfunction of zero sequence protection in 35kV ungrounded system of wind farm","authors":"Liu Zhi-qiang, Liu Wei-ming, Chen Xiao-lu, Liu Chun-Hui, Bai Yun-Peng, Xu Cai","doi":"10.1109/CICED50259.2021.9556659","DOIUrl":null,"url":null,"abstract":"Due to the wind farm 35kV system single-phase grounding fault capacitance current is relatively large, Therefore, the wind farm 35kV system adopts the bus configuration Z-type grounding transformer and the neutral point is grounded by small resistance, Zero sequence protection are used to quickly remove the single phase ground fault.In this paper, the single-phase ground fault of wind power plant collection wire in Eastern Inner Mongoliais is taken as an example. introduces the working principle of zero sequence current transformer,Clarify the setting and matching principles of zero sequence protection,,Comparing the different wiring modes of several cable shielding layers will be cause how Influence on the secondary measurement current of zero-sequence transformer, Analyze the zero sequence protection rejection of the set wire,The cause of the grounding tripping event. Summarizes the cable shield connection mode correctly,And propose rectification measures on site.","PeriodicalId":221387,"journal":{"name":"2021 China International Conference on Electricity Distribution (CICED)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-04-07","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 China International Conference on Electricity Distribution (CICED)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CICED50259.2021.9556659","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Due to the wind farm 35kV system single-phase grounding fault capacitance current is relatively large, Therefore, the wind farm 35kV system adopts the bus configuration Z-type grounding transformer and the neutral point is grounded by small resistance, Zero sequence protection are used to quickly remove the single phase ground fault.In this paper, the single-phase ground fault of wind power plant collection wire in Eastern Inner Mongoliais is taken as an example. introduces the working principle of zero sequence current transformer,Clarify the setting and matching principles of zero sequence protection,,Comparing the different wiring modes of several cable shielding layers will be cause how Influence on the secondary measurement current of zero-sequence transformer, Analyze the zero sequence protection rejection of the set wire,The cause of the grounding tripping event. Summarizes the cable shield connection mode correctly,And propose rectification measures on site.
35kV风电场不接地系统零序保护故障分析
由于风电场35kV系统单相接地故障电容电流比较大,因此,风电场35kV系统采用母线配置z型接地变压器,中性点采用小电阻接地,采用零序保护快速排除单相接地故障。本文以内蒙古东部风电场集线器单相接地故障为例。介绍了零序电流互感器的工作原理,阐明了零序保护的整定与匹配原则,比较了几种电缆屏蔽层的不同接线方式对零序互感器二次测量电流的影响,分析了整定导线的零序保护拒接,接地跳闸事件的原因。正确总结了电缆屏蔽连接方式,并提出了现场整改措施。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信