Coordination between supply power converters and contactors for fault protection in multi-terminal MVDC distribution systems

P. Cairoli, R. Dougal, K. Lentijo
{"title":"Coordination between supply power converters and contactors for fault protection in multi-terminal MVDC distribution systems","authors":"P. Cairoli, R. Dougal, K. Lentijo","doi":"10.1109/ESTS.2013.6523782","DOIUrl":null,"url":null,"abstract":"We present a fast and effective method for detecting and isolating faults in multi-terminal medium voltage dc shipboard power distribution systems. This new detection method permits coordination between the power supply converters and a set of bus segmentizing contactors without requiring fast communication between the elements. The power converters go into current-limiting mode as soon they recognize a fault condition and the segmentizing contactors autonomously decide whether or not to open based on local interpretation of time-to-trip curves as functions of apparent circuit resistance. This method allows converters and contactors to use only local measurements when deciding whether or not to trip in order to isolate the faulted section (later fine tuning can rely on communications). Simulation and experimental results show that faults can be isolated within 10 to 20 ms and the system can be re-energized within 40 to 60 ms.","PeriodicalId":119318,"journal":{"name":"2013 IEEE Electric Ship Technologies Symposium (ESTS)","volume":"20 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2013-04-22","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"25","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2013 IEEE Electric Ship Technologies Symposium (ESTS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ESTS.2013.6523782","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 25

Abstract

We present a fast and effective method for detecting and isolating faults in multi-terminal medium voltage dc shipboard power distribution systems. This new detection method permits coordination between the power supply converters and a set of bus segmentizing contactors without requiring fast communication between the elements. The power converters go into current-limiting mode as soon they recognize a fault condition and the segmentizing contactors autonomously decide whether or not to open based on local interpretation of time-to-trip curves as functions of apparent circuit resistance. This method allows converters and contactors to use only local measurements when deciding whether or not to trip in order to isolate the faulted section (later fine tuning can rely on communications). Simulation and experimental results show that faults can be isolated within 10 to 20 ms and the system can be re-energized within 40 to 60 ms.
多端子MVDC配电系统中电源变流器与接触器故障保护的协调
提出了一种快速有效的船舶多端中压直流配电系统故障检测与隔离方法。这种新的检测方法允许电源转换器和一组总线分割接触器之间的协调,而不需要元件之间的快速通信。电源变换器识别出故障后立即进入限流模式,分段接触器根据视电阻对脱扣时间曲线的局部解释自主决定是否断开。这种方法允许转换器和接触器在决定是否跳闸时仅使用本地测量,以便隔离故障部分(稍后的微调可以依赖于通信)。仿真和实验结果表明,该方法能在10 ~ 20 ms内隔离故障,在40 ~ 60 ms内重新通电。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信