{"title":"Cooperation for aggregating complex electric power networks to ensure system observability","authors":"Usman A. Khan, Marija Ilic, Jose M. F. Moura","doi":"10.1109/INFRA.2008.5439629","DOIUrl":null,"url":null,"abstract":"In this paper, we study the cooperative observability conditions for the local observers formulated on large-scale power systems. A complex large-scale power system model can be considered as a union of several low-dimensional sub-systems where local observers are to implemented. Even if the large-scale system is observable, local observers formulated on such sub-systems may be unstable if the resulting local sub-systems are un-observable. The aggregated effect of the sub-systems, although, may lead to observability. Under certain assumptions, we show that the un-observable local sub-systems can lead to observability by allowing appropriate cooperation among the local observers. In particular, the local error covariances of the local observers can be assimilated such that they preserve a certain (approximated) structure of the global error covariance. This results into stable local observers for un-observable, but, cooperating sub-systems. We provide simulations to assert the findings in the paper.","PeriodicalId":207041,"journal":{"name":"2008 First International Conference on Infrastructure Systems and Services: Building Networks for a Brighter Future (INFRA)","volume":"15 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2008-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"17","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2008 First International Conference on Infrastructure Systems and Services: Building Networks for a Brighter Future (INFRA)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/INFRA.2008.5439629","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 17
Abstract
In this paper, we study the cooperative observability conditions for the local observers formulated on large-scale power systems. A complex large-scale power system model can be considered as a union of several low-dimensional sub-systems where local observers are to implemented. Even if the large-scale system is observable, local observers formulated on such sub-systems may be unstable if the resulting local sub-systems are un-observable. The aggregated effect of the sub-systems, although, may lead to observability. Under certain assumptions, we show that the un-observable local sub-systems can lead to observability by allowing appropriate cooperation among the local observers. In particular, the local error covariances of the local observers can be assimilated such that they preserve a certain (approximated) structure of the global error covariance. This results into stable local observers for un-observable, but, cooperating sub-systems. We provide simulations to assert the findings in the paper.