J. Van Coller, A. Beutel, N. Maphalala, F. Endrejat, J. Msimango
{"title":"Failure of LV ASD supply-side fuses due to MV motor fuse operation","authors":"J. Van Coller, A. Beutel, N. Maphalala, F. Endrejat, J. Msimango","doi":"10.1109/ICIT.2006.372476","DOIUrl":null,"url":null,"abstract":"Transients in MV networks due to MV motor fuse operation can propagate through MV/LV transformers to LV networks. The LV surges can then cause the high-speed fuses protecting LV adjustable speed drives (ASDs) to operate and this can disrupt production. LV ASDs often include supply-side reactors to make them less susceptible to surges (in particular capacitor-switching surges). For the network studied, these reactors did not prevent operation of the particular ASD highspeed fuses. One possible reason was that the supply-side reactors were saturating during the surge conditions associated with MV fuse operation. This paper describes the investigation that included initial measurements, a simulation study so that various proposed solutions could be compared, and final measurements with the final recommended solution in place -supply-side reactors that did not saturate during these surge conditions.","PeriodicalId":103105,"journal":{"name":"2006 IEEE International Conference on Industrial Technology","volume":"5 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-12-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2006 IEEE International Conference on Industrial Technology","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICIT.2006.372476","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1
Abstract
Transients in MV networks due to MV motor fuse operation can propagate through MV/LV transformers to LV networks. The LV surges can then cause the high-speed fuses protecting LV adjustable speed drives (ASDs) to operate and this can disrupt production. LV ASDs often include supply-side reactors to make them less susceptible to surges (in particular capacitor-switching surges). For the network studied, these reactors did not prevent operation of the particular ASD highspeed fuses. One possible reason was that the supply-side reactors were saturating during the surge conditions associated with MV fuse operation. This paper describes the investigation that included initial measurements, a simulation study so that various proposed solutions could be compared, and final measurements with the final recommended solution in place -supply-side reactors that did not saturate during these surge conditions.