Rugi-rugi Daya pada Transformator U.019 PT. PLN 9persero) WS@JB Rayon Ampera Akibat Ketidakseimbangan Beban

Abdul Azis, Nita Nurdiana, Ulfa Lathifatun Nisa
{"title":"Rugi-rugi Daya pada Transformator U.019 PT. PLN 9persero) WS@JB Rayon Ampera Akibat Ketidakseimbangan Beban","authors":"Abdul Azis, Nita Nurdiana, Ulfa Lathifatun Nisa","doi":"10.31851/ampere.v3i1.2145","DOIUrl":null,"url":null,"abstract":"Power losses in distribution transformers can cause neutral currents. Neutral currents in distribution transformers can be caused by load imbalances. This study investigates the load imbalance on the secondary side of the transformer U.019 PT. PLN (PERSERO) Palembang Ampera Rayon. Measurement results and calculations show that if a neutral current load is equalized and power losses due to load imbalance in the distribution transformer are reduced. Unbalanced expense loss due to the neutral current of Peak Expense of 41,5090A and the lowest Expense of 12,1244A so that the percentage of loss in Peak Load loss is 5,3443% and the lowest expense is 1,8562%, and due to the falling unbalanced load voltage is obtained Percentage of Peak Loads of 7.28365% and Lowest Load of 2.43736% of balanced load loss due to neutral currents at balanced load, At Peak Load of 4.9482% and afternoon of 1.7647% and due to balanced load voltage drop in Peak can be 4,94819% and the lowest load can be 1,76471%. The load equalization results in the average peak load that is 262.66667 A with the current load current is IR 262A, IS 263A and IT 263A and at the lowest load average current is 95.0000 A, with a perfect load current IR 94 A, IS 95 A and IT 95 A. Difference Between Unbalanced Charges due to neutral currents with a balanced load at peak loads of 3.961% and the lowest load of 915% while the difference in the voltage drop is unbalanced and balanced at peak load 2.33546% and the Lowest Load amounting to 0.67265% ABSTRAK Rugi-rugi daya pada transformator distribusi dapat menimbulkan arus netral. Arus netra lpad atransformator distribusi dapat disebabkan ketidakseimbangan beban. Penelitian ini menyelidiki ketidakseimbangan beban pada sisise kunder transformator U.019 PT. PLN  (PERSERO) Rayon Ampera Palembang. Hasil pengukuran dan perhitungan menunjukkan bahwaapa bila dilakukan pemerataan beban arus netral dan rugi – rugidayaakibatketidakseimbanganbebanpadatransformatordistribusiberkurang.rugi rugi beban ketidak seimbang akibat arus netral Beban Puncak sebesar 41,5090A dan Beban terendah sebesar  12,1244A sehingga persentase rugi rugi daya Beban Puncak sebesar  5,3443% dan beban Terendah 1,8562% ,dan akibat jatuh tegangan beban ketidak seimbang di peroleh persentase pada Beban Puncak  Sebesar 7,28365%  dan Beban Terendah 2,43736% rugi rugi beban seimbang akibat arus netral pada beban seimbang, Pada Beban Puncak sebesar  4,9482% dan siang 1,7647%  dan akibat jatuh tegangan beban seimbang  Benan Puncak  di dapat 4,94819% dan Beban Terendah di dapat  1,76471%. Hasil pemerataan beban di dapat arus rata rata Beban Puncak  yaitu 262,6667 A dengan arus beban perfasa yaitu I R  262A , I S 263A dan  I T  263A dan pada beban Terendah arus rata rata  yaitu 95,0000 A ,dengan arus beban perfasa yaitu I R 94 A , I S 95 A dan  I T 95 A. Selisih Antara Beban Tidak Seimbang akibat arus netral  dengan beban seimbang pada beban puncak sebesar 3,961% dan beban Terendah sebesar 915% sedangkan selisih pada jatuh tegangan tidak seimbang dan seimbang pada beban puncak 2,33546% dan Beban Terendah sebesar 0,67265%","PeriodicalId":404492,"journal":{"name":"Jurnal Ampere","volume":"600 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2018-06-30","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Jurnal Ampere","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.31851/ampere.v3i1.2145","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

Abstract

Power losses in distribution transformers can cause neutral currents. Neutral currents in distribution transformers can be caused by load imbalances. This study investigates the load imbalance on the secondary side of the transformer U.019 PT. PLN (PERSERO) Palembang Ampera Rayon. Measurement results and calculations show that if a neutral current load is equalized and power losses due to load imbalance in the distribution transformer are reduced. Unbalanced expense loss due to the neutral current of Peak Expense of 41,5090A and the lowest Expense of 12,1244A so that the percentage of loss in Peak Load loss is 5,3443% and the lowest expense is 1,8562%, and due to the falling unbalanced load voltage is obtained Percentage of Peak Loads of 7.28365% and Lowest Load of 2.43736% of balanced load loss due to neutral currents at balanced load, At Peak Load of 4.9482% and afternoon of 1.7647% and due to balanced load voltage drop in Peak can be 4,94819% and the lowest load can be 1,76471%. The load equalization results in the average peak load that is 262.66667 A with the current load current is IR 262A, IS 263A and IT 263A and at the lowest load average current is 95.0000 A, with a perfect load current IR 94 A, IS 95 A and IT 95 A. Difference Between Unbalanced Charges due to neutral currents with a balanced load at peak loads of 3.961% and the lowest load of 915% while the difference in the voltage drop is unbalanced and balanced at peak load 2.33546% and the Lowest Load amounting to 0.67265% ABSTRAK Rugi-rugi daya pada transformator distribusi dapat menimbulkan arus netral. Arus netra lpad atransformator distribusi dapat disebabkan ketidakseimbangan beban. Penelitian ini menyelidiki ketidakseimbangan beban pada sisise kunder transformator U.019 PT. PLN  (PERSERO) Rayon Ampera Palembang. Hasil pengukuran dan perhitungan menunjukkan bahwaapa bila dilakukan pemerataan beban arus netral dan rugi – rugidayaakibatketidakseimbanganbebanpadatransformatordistribusiberkurang.rugi rugi beban ketidak seimbang akibat arus netral Beban Puncak sebesar 41,5090A dan Beban terendah sebesar  12,1244A sehingga persentase rugi rugi daya Beban Puncak sebesar  5,3443% dan beban Terendah 1,8562% ,dan akibat jatuh tegangan beban ketidak seimbang di peroleh persentase pada Beban Puncak  Sebesar 7,28365%  dan Beban Terendah 2,43736% rugi rugi beban seimbang akibat arus netral pada beban seimbang, Pada Beban Puncak sebesar  4,9482% dan siang 1,7647%  dan akibat jatuh tegangan beban seimbang  Benan Puncak  di dapat 4,94819% dan Beban Terendah di dapat  1,76471%. Hasil pemerataan beban di dapat arus rata rata Beban Puncak  yaitu 262,6667 A dengan arus beban perfasa yaitu I R  262A , I S 263A dan  I T  263A dan pada beban Terendah arus rata rata  yaitu 95,0000 A ,dengan arus beban perfasa yaitu I R 94 A , I S 95 A dan  I T 95 A. Selisih Antara Beban Tidak Seimbang akibat arus netral  dengan beban seimbang pada beban puncak sebesar 3,961% dan beban Terendah sebesar 915% sedangkan selisih pada jatuh tegangan tidak seimbang dan seimbang pada beban puncak 2,33546% dan Beban Terendah sebesar 0,67265%
变压器u.019 PT. PLN 9persero) WS@JB Ampera由负载失衡引起
配电变压器的功率损耗会引起中性电流。配电变压器中的中性电流可由负载不平衡引起。本文研究了u019 PT. PLN (PERSERO) Palembang Ampera Rayon变压器二次侧的负载不平衡问题。测量结果和计算结果表明,如果中性电流负载均衡,配电变压器中由于负载不平衡而造成的功率损失就会减少。由于峰值费用的中性电流为41,5090a,最低费用为12,1244 a,因此,在峰值负载损失中所占的损失百分比为5,3443%,最低费用为1,852%,并且由于不平衡负载电压下降,得到平衡负载中中性电流造成的峰值负载损失百分比为7.28365%,最低负载为2.43736%。高峰负荷为4.9482%,下午负荷为1.76477%,由于负载均衡,高峰电压降为494819%,最低负荷降为176471%。负载均衡的结果是平均峰值负载为262.66667 A,当前负载电流为IR 262A, is 263A和IT 263A,最低负载平均电流为950,000 A,完美负载电流为IR 94a, is 95a和IT 95a。峰值负载平衡时中性电流不平衡电荷差值为3.961%,最低负载为915%,峰值负载不平衡电压降差值为2.33546%,最低负载为0.67265%。电网变压器配电业务:电网变压器配电业务:电网变压器配电业务:电网变压器配电业务。Penelitian ini menyelidiki ketidakseimbangan beban padisisiskunder变压器u019 PT. PLN (PERSERO)人造丝Ampera Palembang。Hasil pengukuran丹perhitungan menunjukkan bahwaapa bila dilakukan pemerataan beban阿鲁netral丹rugi——rugidayaakibatketidakseimbanganbebanpadatransformatordistribusiberkurang.rugi rugi beban ketidak seimbang akibat阿鲁netral beban Puncak sebesar 41岁,5090年丹beban terendah sebesar 12日1244 sehingga persentase rugi rugi亚都beban Puncak sebesar 5 3443%丹beban terendah 1 8562%,丹akibat jatuh tegangan beban ketidak seimbang di peroleh persentase篇beban Puncak sebesar7,28365%丹比班Terendah 2,43736% rugi rugi Beban seimbang akibat arus中性帕达比班seimbang,帕达比班punak sebesar 4,9482%丹翔1,76647%丹比班jatuh tegangan巴达班seimbang Benan Puncak di dapat 4,94819%丹比班Terendah di dapat 1,76471%。Hasil pemerataan beban di dapat阿鲁比例分摊比例beban Puncak yaitu 262、6667 dengan阿鲁beban perfasa yaitu ir 262 A, 263我263年代丹T丹篇beban Terendah阿鲁比例分摊比例yaitu 95, 0000 A, dengan阿鲁beban perfasa yaitu ir 94,我95年代丹95 T。seliish Antara, Beban, Tidak, Seimbang, akibar,中性,dangan, Beban, Seimbang, paas, Beban, panak, sebar, 3,961%, Beban, terimbang, sebar, 915%, sedangkan, seliish, paas, jatuh, tegangan, teimbang, Seimbang, paas, Seimbang, Seimbang, 2,33546%, Beban, Terendah, sebar, 0,67265%
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信