Impact of energization current on the safe design of distribution substation earth grid

D. Buba, W. Ahmad, M. A. Kadir, Chandima Gomes, J. Jasni, M. Osman
{"title":"Impact of energization current on the safe design of distribution substation earth grid","authors":"D. Buba, W. Ahmad, M. A. Kadir, Chandima Gomes, J. Jasni, M. Osman","doi":"10.1109/PECON.2014.7062441","DOIUrl":null,"url":null,"abstract":"Energization current is a fundamental consideration in designing of distribution substation earth grid. Arbitrary choice of energization current in earth grid design process may lead to technical and economic implications resulting in underestimated or overestimated designs. In this paper, a distribution substation earth grid was designed using SESCAD and executed in MALT module of CDEGS. The energization current was varied by 100, 75, 50 and 25% of the short circuit current available at the secondary terminals of the upstream transformer to determine the impact on safety criteria of the earth grid. Results indicated that, the EPR for 100% fault current was higher, whereas the step and touch voltages were lower. Also, compared to the other cases of short circuit currents, there was no difference in step and touch voltages when the energization currents were varied at 75, 50 and 25%.","PeriodicalId":126366,"journal":{"name":"2014 IEEE International Conference on Power and Energy (PECon)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2014-03-17","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2014 IEEE International Conference on Power and Energy (PECon)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PECON.2014.7062441","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

Abstract

Energization current is a fundamental consideration in designing of distribution substation earth grid. Arbitrary choice of energization current in earth grid design process may lead to technical and economic implications resulting in underestimated or overestimated designs. In this paper, a distribution substation earth grid was designed using SESCAD and executed in MALT module of CDEGS. The energization current was varied by 100, 75, 50 and 25% of the short circuit current available at the secondary terminals of the upstream transformer to determine the impact on safety criteria of the earth grid. Results indicated that, the EPR for 100% fault current was higher, whereas the step and touch voltages were lower. Also, compared to the other cases of short circuit currents, there was no difference in step and touch voltages when the energization currents were varied at 75, 50 and 25%.
通电电流对配电所地网安全设计的影响
在配电所地网设计中,通电电流是一个基本的考虑因素。在地网设计过程中,任意选择通电电流可能会导致技术和经济影响,从而导致设计被低估或高估。本文利用SESCAD设计了一个配电所地网,并在CDEGS的MALT模块中执行。通电电流按上游变压器二次端可用短路电流的100、75、50和25%变化,以确定对地网安全标准的影响。结果表明,100%故障电流时EPR较高,而步进电压和接触电压较低。此外,与其他短路电流情况相比,当通电电流在75、50和25%时,步进电压和触摸电压没有差异。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信