Pemilihan Kabel Instalasi Listrik Untuk Bangunan Gedung Berdasarkan Kualitas Tahanan Isolasi

Jurnal ELIT Pub Date : 2022-04-04 DOI:10.31573/elit.v3i1.406
Irman Irman, Latifah Latifah, Ruskardi Ruskardi, Muh. Arief
{"title":"Pemilihan Kabel Instalasi Listrik Untuk Bangunan Gedung Berdasarkan Kualitas Tahanan Isolasi","authors":"Irman Irman, Latifah Latifah, Ruskardi Ruskardi, Muh. Arief","doi":"10.31573/elit.v3i1.406","DOIUrl":null,"url":null,"abstract":"The building fire in Pontianak was the result of an electrical short circuit or an electric current, namely the connection between a live conductor and a neutral conductor. Where the electrical installation cables used are generally NYM and NYA cables. \nNYM and NYA cables must be of good quality. This is related to the safety of buildings against fire hazards due to short circuits of electrical cables. For this reason, research is needed in the form of measuring cable insulation resistance to ensure the quality and feasibility of several cable brands on the local market in Pontianak. \nBased on the measurement results on the five test samples, each cable NYM 3 x 2.5 mm2, NYM 2 x 2.5 mm2 and NYA 2.5 mm2, it was found that the NYM cable was 3 x 2.5 mm2 (sample A), NYM cable 2 x 2 .5 mm2 (Sample A) and 2.5 mm2 NYA Cable (sample B) have the highest insulation resistance of the cable sheath compared to 4 (four) other samples, namely 25,010 M Ohm (NYM 3 x 2.5 mm2), 25,425 M Ohm ( NYM 2 x 2.5 mm2) and 39,850 M.Ohm (NYA 2.5 mm2). This shows that these cables have a better quality of sheath insulation resistance than others. While the cables that have the smallest sheath insulation resistance are 11,014 M Ohm (Sample B NYM cable 3 x 2.5 mm2), 10,720 M Ohm (Sample B NYM cable 2 x 2.5 mm2) and 21,580 M.Ohm (Sample A NYA 2.5 mm2) cable.","PeriodicalId":357838,"journal":{"name":"Jurnal ELIT","volume":"84 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-04-04","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Jurnal ELIT","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.31573/elit.v3i1.406","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

The building fire in Pontianak was the result of an electrical short circuit or an electric current, namely the connection between a live conductor and a neutral conductor. Where the electrical installation cables used are generally NYM and NYA cables. NYM and NYA cables must be of good quality. This is related to the safety of buildings against fire hazards due to short circuits of electrical cables. For this reason, research is needed in the form of measuring cable insulation resistance to ensure the quality and feasibility of several cable brands on the local market in Pontianak. Based on the measurement results on the five test samples, each cable NYM 3 x 2.5 mm2, NYM 2 x 2.5 mm2 and NYA 2.5 mm2, it was found that the NYM cable was 3 x 2.5 mm2 (sample A), NYM cable 2 x 2 .5 mm2 (Sample A) and 2.5 mm2 NYA Cable (sample B) have the highest insulation resistance of the cable sheath compared to 4 (four) other samples, namely 25,010 M Ohm (NYM 3 x 2.5 mm2), 25,425 M Ohm ( NYM 2 x 2.5 mm2) and 39,850 M.Ohm (NYA 2.5 mm2). This shows that these cables have a better quality of sheath insulation resistance than others. While the cables that have the smallest sheath insulation resistance are 11,014 M Ohm (Sample B NYM cable 3 x 2.5 mm2), 10,720 M Ohm (Sample B NYM cable 2 x 2.5 mm2) and 21,580 M.Ohm (Sample A NYA 2.5 mm2) cable.
根据隔离犯人的质量选择大楼的电线装置
Pontianak的建筑物火灾是由电气短路或电流引起的,即带电导体和中性导体之间的连接。其中电气安装电缆一般采用NYM和NYA电缆。NYM和NYA电缆必须质量好。这关系到建筑物的安全,防止因电缆短路而发生火灾。因此,需要研究电缆绝缘电阻的测量形式,以确保Pontianak当地市场上几种电缆品牌的质量和可行性。基于五个测试样品的测量结果,每条线缆NYM 3 x 2.5平方毫米,NYM 2 x 2.5平方毫米,那2.5平方毫米,发现NYM电缆3 x 2.5平方毫米(样本),NYM电缆2 x 2。5平方毫米(样品)和2.5平方毫米那电缆绝缘电阻(示例B)最高的电缆护套4(四)其他样品相比,即25010欧姆(NYM 3 x 2.5平方毫米),25425欧姆(NYM 2 x 2.5平方毫米)和39850年M.Ohm(那2.5平方毫米)。这说明这些电缆的护套绝缘电阻质量比其他电缆好。而护套绝缘电阻最小值为11014 M Ohm(样品B NYM电缆3 × 2.5 mm2)、10720 M Ohm(样品B NYM电缆2 × 2.5 mm2)和21580 M Ohm(样品A NYA 2.5 mm2)。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信