{"title":"Harmonics effect on rectifier current imbalance","authors":"V. Gelman","doi":"10.1109/ICHQP.2004.1409453","DOIUrl":null,"url":null,"abstract":"Analyzed data collected during the field test of close coupled 12 pulse rectifier-transformer with wye and delta bridges connected in parallel. Observed the wye delta current imbalance higher then expected based on transformer data. Found the substantial presence of 5/sup th/ harmonic in the incoming line voltage. Provided explanation of measured difference between the wye delta voltages due to harmonics presence. Presented the effect of harmonics on the rectifier current imbalance. Calculated current imbalance based on the observed harmonic content and transformer during the tests.","PeriodicalId":406398,"journal":{"name":"2004 11th International Conference on Harmonics and Quality of Power (IEEE Cat. No.04EX951)","volume":"113 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2004-09-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2004 11th International Conference on Harmonics and Quality of Power (IEEE Cat. No.04EX951)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHQP.2004.1409453","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
Analyzed data collected during the field test of close coupled 12 pulse rectifier-transformer with wye and delta bridges connected in parallel. Observed the wye delta current imbalance higher then expected based on transformer data. Found the substantial presence of 5/sup th/ harmonic in the incoming line voltage. Provided explanation of measured difference between the wye delta voltages due to harmonics presence. Presented the effect of harmonics on the rectifier current imbalance. Calculated current imbalance based on the observed harmonic content and transformer during the tests.