Underfloor air containment

Mikko Pervilä, J. Kangasharju
{"title":"Underfloor air containment","authors":"Mikko Pervilä, J. Kangasharju","doi":"10.1109/OnlineGreenCom.2013.6731035","DOIUrl":null,"url":null,"abstract":"This paper presents Underfloor air containment (UAC), a straightforward extension to Cold Aisle Containment (CAC). Both techniques aim to eliminate air stream mixing and thus reduce the volume of supply air needed for cooling. In UAC the underfloor air supply plenum of a data center is mechanically restricted to the floor sections containing the perforated tiles. We have implemented UAC in our department's 110 kW, 74 m2 data center. Through experimental evaluation and per-tile air velocity measurements, we show that UAC improves the air velocities passing through the perforated tiles in the CAC by 9%. Our solution is light-weight, very low cost, and rapidly installable in other data centers.","PeriodicalId":152857,"journal":{"name":"2013 IEEE Online Conference on Green Communications (OnlineGreenComm)","volume":"2014 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2013-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2013 IEEE Online Conference on Green Communications (OnlineGreenComm)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/OnlineGreenCom.2013.6731035","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2

Abstract

This paper presents Underfloor air containment (UAC), a straightforward extension to Cold Aisle Containment (CAC). Both techniques aim to eliminate air stream mixing and thus reduce the volume of supply air needed for cooling. In UAC the underfloor air supply plenum of a data center is mechanically restricted to the floor sections containing the perforated tiles. We have implemented UAC in our department's 110 kW, 74 m2 data center. Through experimental evaluation and per-tile air velocity measurements, we show that UAC improves the air velocities passing through the perforated tiles in the CAC by 9%. Our solution is light-weight, very low cost, and rapidly installable in other data centers.
地板下空气容器
本文介绍了地板下空气密封(UAC),它是冷通道密封(CAC)的直接扩展。这两种技术都旨在消除气流混合,从而减少冷却所需的供气量。在UAC中,数据中心的地板下送风静压室被机械地限制在包含穿孔瓷砖的地板部分。我们已经在我们部门110千瓦,74平方米的数据中心实施了UAC。通过实验评估和每瓦风速测量,我们发现UAC将通过CAC中穿孔瓦的空气速度提高了9%。我们的解决方案重量轻,成本非常低,并且可以快速安装到其他数据中心。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信