{"title":"Electrode erosion under high current vacuum arcs","authors":"Z. Jiyan, Cheng Lichun","doi":"10.1109/HOLM.1989.77947","DOIUrl":null,"url":null,"abstract":"Electrode erosion was measured under conditions of practical high current and axial magnetic field (AMF). Arc interruptions were made in a demountable vacuum chamber. Electrode erosion was assessed by weighting. It is shown that the rate of electrode erosion with AMF is 39.8 mu g/C and that without AMF it is 1.3 mg/C; the anode gains 15 mu g/C for diffused arcs.<<ETX>>","PeriodicalId":441734,"journal":{"name":"Proceedings of the Thirty Fifth Meeting of the IEEE Holm Conference on Electrical Contacts","volume":"6 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1989-09-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"6","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Proceedings of the Thirty Fifth Meeting of the IEEE Holm Conference on Electrical Contacts","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/HOLM.1989.77947","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 6
Abstract
Electrode erosion was measured under conditions of practical high current and axial magnetic field (AMF). Arc interruptions were made in a demountable vacuum chamber. Electrode erosion was assessed by weighting. It is shown that the rate of electrode erosion with AMF is 39.8 mu g/C and that without AMF it is 1.3 mg/C; the anode gains 15 mu g/C for diffused arcs.<>