{"title":"A New Approach for Calculating Settings of Distance Relays Considering Mutual Coupling Effect","authors":"Zengli Yang, X. Duan","doi":"10.1109/UPEC.2006.367608","DOIUrl":null,"url":null,"abstract":"This paper proposes a new systematic approach for calculating settings of all zones of ground distance relays when mutual coupling effect is considered. The proposed zone 1 setting calculation method is based on the apparent impedance seen by the ground distance relays when faults are simulated on the assumed reach of zone 1. Also, it presents a method for calculating zone 2 and zone 3 settings based on the composite current assistance parameter and apparent impedance in the paper. It is shown that the proposed systematic method guarantees the coverage of zone 1 and increases the sensitivity and accuracy of zone 2 and zone 3 settings","PeriodicalId":184186,"journal":{"name":"Proceedings of the 41st International Universities Power Engineering Conference","volume":"99 12","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-09-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Proceedings of the 41st International Universities Power Engineering Conference","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/UPEC.2006.367608","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3
Abstract
This paper proposes a new systematic approach for calculating settings of all zones of ground distance relays when mutual coupling effect is considered. The proposed zone 1 setting calculation method is based on the apparent impedance seen by the ground distance relays when faults are simulated on the assumed reach of zone 1. Also, it presents a method for calculating zone 2 and zone 3 settings based on the composite current assistance parameter and apparent impedance in the paper. It is shown that the proposed systematic method guarantees the coverage of zone 1 and increases the sensitivity and accuracy of zone 2 and zone 3 settings